AC and DC Voltage Measurement Trms Range: 500 V
Resolution: 0.1 V
Input impedance: 3.3 MΩ
Overload protection: 660 V rms
Continuity Testing (RLO) Range (autoranging): 20 Ω/200 Ω/2000 Ω
Resolution: 0.01 Ω/0.1 Ω/1 Ω
Open circuit voltage: >4 V
Insulation Resistance Measurement (RISO) Test voltages: 50/100/250/500/1000 V
Test voltage: 50 V, Insulation resistance range: 20 MΩ/50 MΩ, Test current: 1 mA at 50 kΩ
Test voltage: 100 V, Insulation resistance range: 20 MΩ/100 MΩ, Test current: 1 mA at 100 kΩ
Test voltage: 250 V, Insulation resistance range: 20 MΩ/200 MΩ, Test current: 1 mA at 250 kΩ
Test voltage: 500 V, Insulation resistance range: 20 MΩ/200 MΩ/500 MΩ, Test current: 1 mA at 500 kΩ
Test voltage: 1000 V, Insulation resistance range: 20 MΩ/200 MΩ/1000 MΩ, Test current: 1 mA at 1 MΩ
Insulation Safety Pretest Requires to connect the tester to L, N and PE
Loop and Line Impedance (ZI) Range: 10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω
Resolution: 1 mΩ/ 0.01 Ω/ 0.1 Ω/1Ω
Prospective Earth Fault Current, PSC Test Range: 1000 A/10 kA (50 kA)
Resolution: 1 A/0.1 kA
Computation: Prospective earth fault current (PEFC) or prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively
RCD Testing, RCD Types Tested RCD Type: AC (responds to AC)
General, no delay
Time delay
Responds to pulsed signal
Responds to smooth DC signal
RCD Trip Time Test (ΔT) Current Settings (1000 mA type AC only. 700 mA maximum type A in VAR mode, VAR mode not available for type B)
10/30/100/300/500/1000 mA – VAR
10/30/100 mA
Multiplier: x½, x 1
Measurement range RCD type G:
310 ms
50 ms
Measurement range RCD type S:
510 ms
160 ms
RCD Trip Current Measurement/Ramp Test (I ΔN) Current range: 30 to 110% of RCD rated current (30 to 150% for Type A IΔN >10 mA)
Step size: 10% of IΔN (5% for Type B)
Dwell time type G: 300 ms/step
Dwell time type S: 500 ms/step
Measurement Accuracy: ±5%
Notes: 30 to 210% for Type A IΔN = 10mA, 20 to 210% for Type B
Specified trip current ranges (EN 61008-1):
50 to 100% for Type AC
35 to 140% for Type A (>10 mA)
35 to 200% for Type A (≤10 mA)
50 to 20 % for Type B
Earth Resistance Test (RE) Range: 200 Ω/2000 Ω
Resolution: 0.1 Ω/1 Ω
Frequency: 128 Hz
Output voltage: 25 V
Phase Sequence Indicaton Icon: Phase sequence indicator is active
Range: 100 to 500 V
Display: “1-2-3″: or “3-2-1″
Performance EC/EN61557-1 to IEC/EN61557-7 and IEC/EN61557-10
Overvoltage CAT III 500 V, CAT IV 300 V
Safety Complies with IEC/EN61010-1, UL61010, ANSI/ISA –s82.02.01 and CAN/CSA c22.2 No. 1010
Sealing IP 40
Battery 1.5 V type AA (IEC LR6), 6 pcs
Dimensions 3.93 x 9.84 x 4.92″ (10 x 25 x 12.5 cm)
Weight Approximately 2.86 lbs (1.3 kg) including batteries